Answered Questions

  • What is the power ratio between power in Star and Delta circuit?

    Star Read Best Answer

    Editorial / Best Answer

    KaranSorout  

    • Member Since Jul-2006 | Jul 13th, 2006


    The power ratio between Star to Delta is 1:3

    Explanation:

     

    Let?s suppose Vs be the supply voltage per phase.

    So the line voltage of the supply will be ?3Vs.

    Now assume any type of load; for simplicity I?m assuming it a only resistive load.

    And let it be ?R? per phase.

     

    For Delta connected load:

     

    Calculation for per phase power; PD= I2R

     

    Where I ? load current (per phase)

    And,

    I = ?3Vs/R       {as line voltage of the supply is directly applied to the phase of the delta load}

    So,

                Pd = (?3Vs/R )2R = 3Vs2/R  watts per phase.

    For 3 phases:

                P3D = 3Pd = 3*3Vs2/R = 9Vs2/R watts.

     

    Now for Star connected load:

     

    PS = I2R = (Vs/R)2R = Vs2/R watts

    For 3 phases: P3S = 3PS = 3 Vs2/R watts

     

    Conclusion:

    P3S / P3D  =  3Vs2/R / 9Vs2/R = 1/3

    It may be better concluded by drowing figures. If any variations, can connect to me through karan.sorout@gmail.com  

    RUP KAMAL KUTUM

    • Feb 3rd, 2018

    Well first you assumed voltage per phase as Vs and Line voltage as sqrt(3) x Vs: Which is for star connection. Then, you assumed the same thing for Delta Connection(where line and phase voltages are t...

    Anbumozhi R

    • Dec 3rd, 2017

    Power is Same. Whether it is star to Delta conversion or Delta to star conversion. Power is 1:1