  • For a 100kw generator, only 50kw of load is connected. Will the generator generate only 50kw or 100kw? If it generate 100kw what happens to rest of the 50kw. What happens if we connect more than 100kw of load?

    Star Read Best Answer

    Editorial / Best Answer

    Answered by: joe

    • Dec 23rd, 2006


    100 kw is the full load rating of the generator..... ..that means it can supply 100 kw without exceeding in specified temperature limits .that doesnt mean that it wont be able to supply a load more than 100 kw,it can but not for a longer period of time.after sometime the generator will burn out.if a load of 50 kw is connected to generator the generator will generate only 50 kw& not more than that.the generator will generate power only according to the requirement.

    Dharmender

    • Feb 7th, 2018

    Connected Load is 96kw &125kvaDG set will have run stand by unit for Hotel is suitable plz give your technical supporting answer

    Mayilsamy Kasipandi

    • Jul 11th, 2017

    The Generator produce the power is exactly what we withdraw as load. 100 kw genset can produce 1 kw to 115kw power depending upon the connected/withdrawing load. Normally the generator can produce 115% of designed rating.

  • What is the power ratio between power in Star and Delta circuit?

    Star Read Best Answer

    Editorial / Best Answer

    KaranSorout  

    • Member Since Jul-2006 | Jul 13th, 2006


    The power ratio between Star to Delta is 1:3

    Explanation:

     

    Let?s suppose Vs be the supply voltage per phase.

    So the line voltage of the supply will be ?3Vs.

    Now assume any type of load; for simplicity I?m assuming it a only resistive load.

    And let it be ?R? per phase.

     

    For Delta connected load:

     

    Calculation for per phase power; PD= I2R

     

    Where I ? load current (per phase)

    And,

    I = ?3Vs/R       {as line voltage of the supply is directly applied to the phase of the delta load}

    So,

                Pd = (?3Vs/R )2R = 3Vs2/R  watts per phase.

    For 3 phases:

                P3D = 3Pd = 3*3Vs2/R = 9Vs2/R watts.

     

    Now for Star connected load:

     

    PS = I2R = (Vs/R)2R = Vs2/R watts

    For 3 phases: P3S = 3PS = 3 Vs2/R watts

     

    Conclusion:

    P3S / P3D  =  3Vs2/R / 9Vs2/R = 1/3

    It may be better concluded by drowing figures. If any variations, can connect to me through karan.sorout@gmail.com  

    RUP KAMAL KUTUM

    • Feb 3rd, 2018

    Well first you assumed voltage per phase as Vs and Line voltage as sqrt(3) x Vs: Which is for star connection. Then, you assumed the same thing for Delta Connection(where line and phase voltages are t...

    Anbumozhi R

    • Dec 3rd, 2017

    Power is Same. Whether it is star to Delta conversion or Delta to star conversion. Power is 1:1